PRODUCT

view-page01

6kw 2Rack Standard Cooler

Air-cooled cooler UL certified
  • Cooling system
    Air-cooled system
  • Maximum operating power
    6.5 kW
  • Cooling Capacity
    6,000W
  • Standard(mm)
    700 X 600 X900

Details

Model 6,000W
Standard / 2 Rack
Air Cooled Chiller UL Certificated
Temperature range control method Operation Water Temp. – 5 ~ 30
Ambient Temp. – 30 ~ 50
Coolant type E.G / P.G / Water
Capacity Cooling Capacity W 6,000
Heater Capacity W 2,000
Electrical Specifications Power Supply Range V / Ph / Hz 208 × 3 × 60
Rated Operating Power kW 2.5
Rated Operating Current A 10.2
Max Operating Power kW 6.5
Max Current A 26.8
Control Control Type Temp', Flow Rate, Pressure, DP Auto Control
Control Operating Power VDC 24
Communication Cable Shielded Cable AWG20(0.75SQ) × 3C
Outside Spec. Dimensions(mm) W × D × H 700 × 600 × 900
Weight (Transfort + Tank Volume) kg 160 (140 + 20)
certification / IP Code Unit Color UL60335-2-40 / CE / IEC60529 IP55
Noise dB(A) ≤79
ISO12944 Paint / Unit Color C5H / Option
Refrigerant R32
Compressor Type SCROLL / BLDC Motor
Rated Operating Power / Max Operating Power kW / kW 1.9 / 3.9
Amount Set 1
Rated Operating Current A 7.3
Max. Current A 14.9
Condenser Type Fin-Tube
Condensor Fan Fan & Motor kW Axial Fan Φ450 / 0.20 W
Amount Set 1
Max Operating Power kW 0.20
Motor Current A 0.9
Evaporator Type Compact Brazed Plate
Pump & Motor Model / Manufacturer CM1-2(sus) / Grundfos
Circulation Flow Rate lpm 37 ~ 45
Motor Power kW 0.43
Motor Current A 1.95
Water Tank Tank Volume Liter 20
Water Line Material Copper, SUS 304
Pipe Diameter (In / Out) mm 25
Supply / Drain mm 10
Heater Cap Heater Cap.(Current) kW / A 2.00 / 9.09

Please note that some parts may be changed to improve product performance. Part specifications are subject to change for better performance.

© HDC. ALL RIGHTS RESERVED.